The aim of seasonal commissioning is to observe the building services when they are run at their full load and ensure they perform as the were designed to. This has proved to be a valuable and crucial service for all building types, a building with fewer defects performs better.
The continuous support of the commissioning team during the first year reduces the operation and maintenance costs as defects are identified and rectified earlier, increasing the systems’ life.
Training undertaken as part of the commissioning helps the building occupants and facilities managers better understand the functionality of the building and ensure it continues to perform at optimum levels.
[edit] When to consider
A commitment to carry out seasonal commissioning will be required at the design stage. Seasonal commissioning should commence during the first 12 months after the building is occupied and take place during full load conditions (i.e. heating equipment in mid-winter and cooling/ventilation during summer) and part load conditions (spring/autumn)
[edit] Step-by-step guidance
The requirements of this credit are an extension of the normal responsibilities for a contractor where there is a 12 months defects period in place under the contract and contributes to providing a 'soft landing' for the client/occupier.
The contractor is required to confirm that a specialist commissioning manager has been appointed to carry out seasonal commissioning during the first 12 months after occupation. Under the BREEAM criteria, there are a number of systems defined as complex and it is unlikely that a single person will have sufficient experience to undertake this role for all systems. Therefore the contractor may need to appoint more than one individual to this role.
Ideally, as part of the design stage, the contractor should nominate named individuals to undertake this role in particular where the Man 04 credit on commissioning building services has been targeted as the same people can carry out both roles. However, if this is not appropriate, commitment to make the appointment would be sufficient.
For simple systems, this role can either be undertaken by the contractor or the client/occupier can nominate an individual from within their facilities management team to undertake the required activities. Where the client/occupier has nominated an individual to monitor the commissioning of the systems on their behalf, this person could also perform this role.
[edit] Questions to ask while seeking compliance
- Are complex systems present within the building design?
- Can the role of the specialist commissioning manager appointed for Man 04 be extended to meet the requirements of this credit?
[edit] Tools and resources
- BSRIA Commissioning guides and CIBSE Commissioning codes.
- Knowledge Base Link for Man05: Aftercare: https://kb.breeam.com/section/new-construction/uk/2014-uk/management-breeam_uk_nc_2014/man05/
[edit] Tips and best practice
Where a building management system (BMS) is specified the following procedures should be carried out:
- The occupier is fully trained in the operation of the system.
- All BMS graphics and schematics are fully functional and installed to user interface before handover.
- The BMS/ controls installation should be running in auto with satisfactory internal conditions prior to handover.
- In addition to air and water flow results, commissioning results include physical measures of air temperatures, off coil temperatures and other key parameters as appropriate.
- Commissioning of air and water systems is carried out when all control devices are installed, wired and functional.
[edit] Typical evidence
[edit] Design stage
A specification, contract clauses or appointment letter confirming the commitment to carry out commissioning during the first 12 months of occupation. Where complex systems are installed, a specialist commissioning manager must be appointed.
[edit] Post construction
Copies of an appointment letter confirming seasonal commissioning responsibilities and seasonal commissioning schedules confirming what will be commissioned and when. Where seasonal commissioning has already taken place due to the timing of the post construction assessment, records and reports to confirm this has taken place should be provided.
[edit] Applicable Schemes
The guidelines collated in this ISD aim to support sustainable best practice in the topic described. This issue may apply in multiple BREEAM schemes covering different stages in the life of a building, different building types and different year versions. Some content may be generic but scheme nuances should also be taken into account. Refer to the comments below and related articles to this one to understand these nuances. See this document for further guidelines.
- BREEAM UK New Construction 2014
- BREEAM UK Refurbishment and Fit-Out 2014
This article was originally created in a BREEAM Professionals workshop by Jane Morning, Tom Blois-Brooke, Tom Abbott and Azita Dezfouli.
BRE Global does not endorse any of the content posted and use of the content will not guarantee the meeting of certification criteria.
--Multiple Author Article 16:26, 19 Apr 2018 (BST)
[edit] Related articles on Designing Buildings Wiki
- Advantages of shell and core.
- At your services - What to expect during commissioning.
- Client commissioning.
- Commissioning.
- Commissioning documents.
- Commissioning notice.
- Commissioning plan.
- Commissioning planning.
- Commissioning v testing.
- Continuous commissioning.
- Corrosion in heating and cooling systems.
- Handover to client.
- Initial commissioning case studies.
- Seasonal and continuous commissioning.
- continuous commissioning
- Soft landings.
- Specialist commissioning manager.
Featured articles and news
About the 5 Percent Club and its members
The 5% Club; a dynamic movement of employers committed to building and developing the workforce.
New Homes in New Ways at the Building Centre
Accelerating the supply of new homes with MMC.
Quality Planning for Micro and Small to Medium Sized Enterprises
A CIOB Academy Technical Information sheet.
A briefing on fall protection systems for designers
A legal requirement and an ethical must.
CIOB Ireland launches manifesto for 2024 General Election
A vision for a sustainable, high-quality built environment that benefits all members of society.
Local leaders gain new powers to support local high streets
High Street Rental Auctions to be introduced from December.
Infrastructure sector posts second gain for October
With a boost for housebuilder and commercial developer contract awards.
Sustainable construction design teams survey
Shaping the Future of Sustainable Design: Your Voice Matters.
COP29; impacts of construction and updates
Amid criticism, open letters and calls for reform.
The properties of conservation rooflights
Things to consider when choosing the right product.
Adapting to meet changing needs.
London Build: A festival of construction
Co-located with the London Build Fire & Security Expo.
Tasked with locating groups of 10,000 homes with opportunity.
Delivering radical reform in the UK energy market
What are the benefits, barriers and underlying principles.
Information Management Initiative IMI
Building sector-transforming capabilities in emerging technologies.
Recent study of UK households reveals chilling home truths
Poor insulation, EPC knowledge and lack of understanding as to what retrofit might offer.